Operating manual 106Heating circuit controller with differential temperature Version 0933-10Art. 0450021003BA_CETA106_EbV_EN_0450021003_0933-10.book
Parameter description86. Parameter description01 Information levelDisplay Designation Description03:01 Outdoor actual Current outside temperature03:02
9Parameter description02 Time programsNote: When switch-on and switch-off time are the same, cycle of operation is switched off.03 Parameter systemWee
Parameter description1006 Parameter heating circuit03:04 Building type Setting range: 1: Light construction (mean value over 6 X3 hours)2: Medium c
11Parameter description06:02 Room day Setting range: 5 … 30°CFactory setting: 30°CFunction:The set temperature is the room setpoint during active cycl
Parameter description1206:07 Heating curve/conductanceSetting range: 0,05 … 3,50Factory setting: 1,00Function:Determines the heating curve for the hea
13Parameter description06:09 Frost protection Setting range: OFF (----) X3-50 °C ... +10 °CFactory setting: 3 °CFunction:To keep the heating system fr
Parameter description1408 Parameter Delta-T06:18 Minimum temperature limitSetting range: 5…95°C X3Factory setting: 20°CFunction:This function limits t
15Parameter description08:04 Minimum running time of pumpSetting range: OFF (----)0.5 ... 60 minFactory setting: 3 minFunction:Minimum switch-on time
15 Parameter description Display Designation Description 08:18 Back Cooling Setting range: OFF (----), 5 ... 50K Differential Factory sett
Parameter description1626 Time setting27 Sensor calibration08:10 Inhibition heat generatorSetting range: OFF (----) ... 24h Function:After burner blo
Scope of delivery ...1General ...
17Mounting28 Relay test7. MountingDrilling pattern for wall fasteningDisplay Designation Description28:01 Test output 1 Setting range: 0 = OFF1 = ONFa
Connection diagram18Rail mount8. Connection diagram1. Insert mounting feet into rail mount opening.2. Lock hook in place by pushing down.Hazard!Connec
19Fault clearance9. Fault clearanceTo allow an accurate diagnosis in case of malfunction, the unit is equipped with a fault display system. The faults
Sensor resistance values2010. Sensor resistance valuesDepending on temperature:PT1000 (option) VF202B, AF200, KVT20 (option)T (°C) R (kOhm) T (°C) R (
21Declaration of conformity11. Declaration of conformityElektronikbau- und Vertriebs- GmbH Heisternerweg 8-12, 57299 BurbachEC Declaration of Conf
Technical Data2212. Technical Data13. LiabilityOur general terms and conditions of business are generally applicable. Any liability claims based on fa
1Scope of deliveryGeneralSystems with mixed heating circuit are controlled via the heating circuit controller. Required heating circuit temperature is
General key functions21. General key functionsProg•Change selected submenus•Change (parameter) setting•Save value+ (Plus) or - (Minus)•Change paramete
3Basic display3. Basic displayExplanation of symbolsWeekday14:47 Time44.0°C Temperature F1 heat storage tank 1Display pump function ΔTDisplay pump fun
Functions with direct access44. Functions with direct accessManual operation— Activate by pressing and holding button — End function by pressing butto
5Menu level5. Menu levelBasic displayProgEsc01Menu 0102Menu 02+-27Calibration28Relay test02:01Parameter 0102:02Parameter 0202:nnLast parameter+-+-+-+-
Menu level6Overview of menu levelX2: Function only in bus connectionX3: Are hidden when activating code 03:09X4: Only when connecting CETA RCBasic dis
7Menu level06:02Mixing valveopen/closed06:03Flow actual06:04Flow setpoint03:06Time for automatic exit06:05Room actual06:06Room setpoint03:07Anti-block